Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 4, 2017, 12:12 PM
  • 02 0724_02 0723_04122017_041257.mp4

Date
12/04/2017
W/O
674429
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00294
PipeID
P03278
Time
4:12 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5258
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
29
Purpose
Routine Assessment
Project
WO_674429_TV02351_DEC2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0724
Downstream MH
02 0723
Dir. of Survey
Downstream
Length Surveyed
254.6 ft.
Total Length
254.6 ft.
Structural Index
3
Structural Quick
3G23
Structural Rating
130
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
130
Pipe schematic from manhole 02 0724 to 02 0723
MH: 02 0724MH: 02 0723downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 072410.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"13.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"26.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES31.9 ft. CC - Crack Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES39.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start47.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish47.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start104.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"106.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"222.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"227.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"254.6 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK254.6 ft. AMH - Downstream Manhole, Survey Ends - 02 0723254.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    26.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES

    31.9 ft. - Crack Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    39.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    47.7 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
227.1TFC
0MWL
254.6MGOCONNECTION AT MH 9 O'CLOCK
39.7CL
47.7CL
26.2CL
104.7TF
10.6TFC
254.6AMH02 0723
222.8TFC
0MWM
0AMH02 0724
47.7CM
31.9CC
13.3TFC
106.6TFC
254.6CM

Properties (4)

additional_info
SC346287
custom_field_two
3
customer
LACSD
datetime
2017-12-04T04:12:47-08:00