Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 29, 2017, 05:57 AM
  • 02 1303_02 1302_28112017_215847.mp4

Date
11/28/2017
W/O
673943
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03822
Time
9:57 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5053
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_673943_TV02329_DEC2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1303
Downstream MH
02 1302
Dir. of Survey
Downstream
Length Surveyed
326.2 ft.
Total Length
326.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
1
O&M Quick
211E
O&M Rating
33
Overall Index
1
Overall Quick
Overall Rating
36
Pipe schematic from manhole 02 1303 to 02 1302
MH: 02 1303MH: 02 1302downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 13030 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area3.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start42.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"68 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES74.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start93.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"144.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"199.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"227 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO227 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish245.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"250.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"254.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"281.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"297.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"326.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish326.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1302326.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    74.6 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
144.9TFA
281.8TB
326.2CM
245.7TFC
326.2AMH02 1302
74.6RFJ
297.7TFC
227DSZ
3.1CM
254.3TF
250.7TF
0AMH02 1303
227RFJ
68RFJ
326.2MGOCONNECTION AT MH 3 O'CLOCK
93.7TF
0MWM
199.2TF
0MWL
42.5TF

Properties (4)

additional_info
SC346282
custom_field_two
3
customer
LACSD
datetime
2017-11-28T21:57:54-08:00