Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 28, 2017, 10:19 AM
  • 02 1312_02 1311_28112017_021948.mp4

Date
11/28/2017
W/O
673943
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03832
Time
2:19 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5052
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
WO_673943_TV02329_DEC2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1312
Downstream MH
02 1311
Dir. of Survey
Downstream
Length Surveyed
363.5 ft.
Total Length
363.5 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
216
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
216
Pipe schematic from manhole 02 1312 to 02 1311
MH: 02 1312MH: 02 1311downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 13120 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CAPPED LATERAL 3 O'CLOCK @ MH0 ft. MWM - Water Mark, 15 %of cross sectional area3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start41.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"82.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"90.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"98 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"113.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"131.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"136.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"182.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"185.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"187.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"226.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"231.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"272.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"275.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"291 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"296 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"351.2 ft. MGO - General Observation - JOINT BROKEN363.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish363.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1311

Observation photos (2)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - JOINT BROKEN

    351.2 ft. - General Observation - JOINT BROKEN

Observations (24)

DistanceCodeObservation
351.2MGOJOINT BROKEN
41.5TF
82.5TFC
291TF
275.2TF
0AMH02 1312
272.8TF
0MWL
113.4TF
226.3TF
182.8TF
136.6TF
0MGOCAPPED LATERAL 3 O'CLOCK @ MH
231.8TF
296TF
363.5CM
187.9TB
3CM
0MWM
98TFC
90.1TB
131.4TF
363.5AMH02 1311
185.1TFC

Properties (4)

additional_info
SC346281
custom_field_two
3
customer
LACSD
datetime
2017-11-28T02:19:30-08:00