Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 29, 2017, 07:19 AM
  • 02 1297_02 1296_28112017_231955.mp4

Date
11/28/2017
W/O
673943
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03814
Time
11:19 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5053
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_673943_TV02329_DEC2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1297
Downstream MH
02 1296
Dir. of Survey
Downstream
Length Surveyed
278.5 ft.
Total Length
278.5 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
162
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
162
Pipe schematic from manhole 02 1297 to 02 1296
MH: 02 1297MH: 02 1296downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 12970 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area3.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: NO, Start4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"32.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"42.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"80.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"84.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"85.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"92.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"125.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"127.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"132.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"132.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"204.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"206.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"210.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"242.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"273.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish278.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1296

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    3.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

Observations (21)

DistanceCodeObservation
92.2TF
278.5AMH02 1296
132.7TFC
0AMH02 1297
0MWM
127.2TF
125.9TB
0MWL
4TF
42.2TF
84.7TFC
210.7TF
132.7TF
32.6TF
206.8TF
80.5TF
273.5CM
242.4TF
3.1CM
204.5TF
85.7TF

Properties (4)

additional_info
SC346282
custom_field_two
3
customer
LACSD
datetime
2017-11-28T23:19:23-08:00