Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 28, 2017, 09:46 AM
  • 02 1314_02 1313_28112017_014645.mp4

Date
11/28/2017
W/O
673943
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00238
PipeID
P03834
Time
1:46 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5052
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
WO_673943_TV02329_DEC2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1314
Downstream MH
02 1313
Dir. of Survey
Downstream
Length Surveyed
311.7 ft.
Total Length
311.7 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
183
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
183
Pipe schematic from manhole 02 1314 to 02 1313
MH: 02 1314MH: 02 1313downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 13140 ft. MWL - Water Level, 10 %of cross sectional area3.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start79 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"84.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"101.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"132.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"150.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"183.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"191 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"234.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"246.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"249.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"282.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"308.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311.7 ft. AMH - Downstream Manhole, Survey Ends - 02 1313311.7 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
246.9TF
3.1CM
282.5TF
311.7AMH02 1313
84.4TFC
311.7MGOCONNECTION AT MH 3 O'CLOCK
0MGOCONNECTION AT MH 9 O'CLOCK
191TF
0MWM
150.4TF
101.9TF
0MGOCONNECTION AT MH 3 O'CLOCK
0AMH02 1314
183.3TF
234.1TF
308.2CM
249.4TF
0MWL
79TF
132.4TF

Properties (4)

additional_info
SC346281
custom_field_two
3
customer
LACSD
datetime
2017-11-28T01:46:27-08:00