Section#3_A 0513_A 0512__1122018__G6915.mp4
2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT
2 ft. - General Observation - MAG COAT 99% START 8:00 TO 4:00
8 ft. - General Observation - THICK MAG COAT
45.9 ft. - Surface Reinforcement Visible, from 12 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT
50.8 ft. - Surface Reinforcement Visible, from 11 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR INDER MAG COAT
66 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR UNDER MAG COAT
85.3 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR
197.8 ft. - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBVAR UNDER MAG COAT
234.4 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CORRODED REBAR UNDER MAG COAT
266.8 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR
584.8 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR
| Distance | Code | Observation |
|---|---|---|
| 85.3 | SRV | CIRCUM REBAR |
| 45.9 | SRV | CIRCUM REBAR UNDER MAG COAT |
| 2 | SAM | SEVERE AGG UNDER MAG COAT |
| 785 | SAM | SEVERE AGG |
| 66 | SRV | CIRCUM REBAR UNDER MAG COAT |
| 234.4 | SRC | CORRODED REBAR UNDER MAG COAT |
| 0 | AMH | 4:20AM |
| 584.8 | SRV | CIRCUM REBAR |
| 0 | MWL | — |
| 50.8 | SRV | CIRCUM REBAR INDER MAG COAT |
| 785.6 | AMH | 5:25AM |
| 0 | MWM | — |
| 785 | SRV | CIRCUM REBAR UNDER MAG COAT |
| 785 | SRC | CIRCUM REBAR UNDER MAG COAT |
| 197.8 | SRC | CIRCUM REBVAR UNDER MAG COAT |
| 785 | MGO | MAG COAT 99% FINISH |
| 2 | MGO | MAG COAT 99% START 8:00 TO 4:00 |
| 266.8 | SRV | CIRCUM REBAR |
| 8 | MGO | THICK MAG COAT |