Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 10, 2018, 04:08 PM
  • Section#1_A 0041_A 0040__1102018__G6914.mp4

Date
01/10/2018
W/O
0679336
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00334
PipeID
P08416
Time
8:08 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6914
Sewer Name
A JOINT OUTFALL A - UNIT 3C
City
COMPTON
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
09
Purpose
Capital Improvement Program Assesment
Project
20180110SHO_JOINT_OUTFALL_A_UNIT_3C
Material
RCP-CTL
Shape
Square
Height
78 in.
Width
78 in.
Upstream MH
A 0041
Downstream MH
A 0040
Dir. of Survey
Downstream
Length Surveyed
694.5 ft.
Total Length
694.5 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole A 0041 to A 0040
MH: A 0041MH: A 0040downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 10500 ft. MWL - Water Level, 40 %of cross sectional area8 ft. MGO - General Observation - 80% MAG COAT INTACT8 ft. SAP - Surface Aggregate Projecting, at 12 o'clock, within 8 inches of joint: NO46.5 ft. MGO - General Observation - POSSIBLE REBAR STICKING OUT54.4 ft. MGO - General Observation - POSSIBLE REBAR HANGING DOWN62.8 ft. MGO - General Observation - 100% TILES MISSING135.4 ft. MGO - General Observation - 50% TILES MISSING320.1 ft. MGO - General Observation - 0% TILES MISSING402.8 ft. MGO - General Observation - 30% TILES MISSING596.2 ft. OBZ - Obstacles Other, 10 %of cross sectional area, from 09 to 11 o'clock - POSSIBLY RAGS CAUGHT ON BROKEN REBAR694.5 ft. MSA - Survey Abandoned - BOAT FLIPPED OVER

Observation photos (7)

  • Surface Aggregate Projecting, at 12 o'clock, within 8 inches of joint: NO

    8 ft. - Surface Aggregate Projecting, at 12 o'clock, within 8 inches of joint: NO

  • General Observation - POSSIBLE REBAR STICKING OUT

    46.5 ft. - General Observation - POSSIBLE REBAR STICKING OUT

  • General Observation - POSSIBLE REBAR HANGING DOWN

    54.4 ft. - General Observation - POSSIBLE REBAR HANGING DOWN

  • General Observation - 100% TILES MISSING

    62.8 ft. - General Observation - 100% TILES MISSING

  • General Observation - 50% TILES MISSING

    135.4 ft. - General Observation - 50% TILES MISSING

  • General Observation - 0% TILES MISSING

    320.1 ft. - General Observation - 0% TILES MISSING

  • Obstacles Other, 10 %of cross sectional area, from 09 to 11 o'clock - POSSIBLY RAGS CAUGHT ON BROKEN REBAR

    596.2 ft. - Obstacles Other, 10 %of cross sectional area, from 09 to 11 o'clock - POSSIBLY RAGS CAUGHT ON BROKEN REBAR

Observations (13)

DistanceCodeObservation
46.5MGOPOSSIBLE REBAR STICKING OUT
596.2OBZPOSSIBLY RAGS CAUGHT ON BROKEN REBAR
0MWM
0AMH1050
694.5MSABOAT FLIPPED OVER
320.1MGO0% TILES MISSING
402.8MGO30% TILES MISSING
54.4MGOPOSSIBLE REBAR HANGING DOWN
8MGO80% MAG COAT INTACT
62.8MGO100% TILES MISSING
135.4MGO50% TILES MISSING
0MWL
8SAP

Properties (5)

additional_info
RFIR
custom_field_three
BOAT FLIPPED OVER
custom_field_two
5
customer
LACSD
datetime
2018-01-10T08:08:12-08:00