Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 6, 2018, 12:16 PM
  • Section#15_05 0279_04 0278__162018__G6908.mp4

Date
01/06/2018
W/O
0682489
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00498
PipeID
P05486
Time
4:16 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6908
Sewer Name
05 OAK STREET-CENTER AVENUE TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20180105MDM_OAK_STREET_CENTER_AVENUE_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
05 0279
Downstream MH
04 0278
Dir. of Survey
Downstream
Length Surveyed
320.5 ft.
Total Length
320.6 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
323
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
323
Pipe schematic from manhole 05 0279 to 04 0278
MH: 05 0279MH: 04 0278downstream0 ft. AMH - Upstream Manhole, Survey Begins - 6:50AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - MH CONN 9:00 ACTIVE2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG8.2 ft. MGO - General Observation - 27" RCP181.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG320.2 ft. MGO - General Observation - MH CONN 9:00 ACTIVE320.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE320.2 ft. MGO - General Observation - MH CONN 3:00 ACTIVE320.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG320.6 ft. AMH - Downstream Manhole, Survey Ends - 7:10AM

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - 27" RCP

    8.2 ft. - General Observation - 27" RCP

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    181.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (13)

DistanceCodeObservation
320.2MGOMH CONN 9:00 ACTIVE
0AMH6:50AM
320.2SSSBLISTERING PEELING CONCRETE
320.6AMH7:10AM
2SSSBLISTERING PEELING CONCRETE
8.2MGO27" RCP
0MWL
320.2MGOMH CONN 3:00 ACTIVE
0MWM
2SAPSEVERE AGG
320.2SAPSEVERE AGG
181.3SAPSEVERE AGG
0MGOMH CONN 9:00 ACTIVE

Properties (4)

custom_field_three
SEVERE AGG PROJECTING
custom_field_two
3
customer
LACSD
datetime
2018-01-06T04:16:05-08:00