Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 24, 2017, 08:03 AM
  • F 0153_F 0152_02242017_000431.mp4

Date
02/24/2017
W/O
626078
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00038
PipeID
P10185
Time
12:03 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4253
Sewer Name
F JOINT OUTFALL F - UNIT 3C
City
NORWALK
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
WO_626078_DISTRICT02_MAR2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Width
54 in.
Upstream MH
F 0153
Downstream MH
F 0152
Dir. of Survey
Downstream
Length Surveyed
1326.4 ft.
Total Length
1326.4 ft.
Structural Index
3
Structural Quick
533t
Structural Rating
810
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
814
Pipe schematic from manhole F 0153 to F 0152
MH: F 0153MH: F 0152downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 01530 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start19 ft. SMW - Surface Missing Wall, from 02 to 03 o'clock, within 8 inches of joint: YES, Start34.4 ft. SMW - Surface Missing Wall, from 02 to 03 o'clock, within 8 inches of joint: YES, Finish59.6 ft. MGO - General Observation - MAG CCOATING811.8 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"1325.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish1326.4 ft. AMH - Downstream Manhole, Survey Ends - F 0152

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Missing Wall, from 02 to 03 o'clock, within 8 inches of joint: YES, Start

    19 ft. - Surface Missing Wall, from 02 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWM
59.6MGOMAG CCOATING
811.8TBA
1325.8SAP
0MWL
1326.4AMHF 0152
0AMHF 0153
34.4SMW
2SAP
19SMW
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK

Properties (4)

additional_info
SC306956
custom_field_two
1
customer
LACSD
datetime
2017-02-24T00:03:08-08:00