Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2017, 06:37 AM
  • 29 0274_29 0273 _16032017_233747.mpg

Date
03/16/2017
W/O
624460
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00550
PipeID
P24182
Time
11:37 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4383
Sewer Name
29 WEST HILL STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
WO_624460_TV29035_MAR2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0273
Downstream MH
29 0274
Dir. of Survey
Upstream
Length Surveyed
252.4 ft.
Total Length
252.5 ft.
Structural Index
3
Structural Quick
3522
Structural Rating
20
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
24
Pipe schematic from manhole 29 0273 to 29 0274
MH: 29 0273MH: 29 0274upstream0 ft. AMH - Upstream Manhole, Survey Ends - 29 02740.3 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"2.2 ft. JOM - Joint Offset Medium2.6 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"5.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"11.4 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"56.1 ft. CM - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES56.1 ft. RFB - Roots Fine Barrell, from 09 to 10 o'clock65.3 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"77.2 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES80.6 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"86.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"98.1 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"108.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"122.2 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"125.7 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"148.8 ft. CM - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES151.9 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"164.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"166.8 ft. RFB - Roots Fine Barrell, from 02 to 04 o'clock - COMING FROM CRACK166.8 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES167.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"199.8 ft. CM - Crack Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES206.6 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"218.2 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES229.6 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES246 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"248.6 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"252.5 ft. MWM - Water Mark, 5 %of cross sectional area252.5 ft. AMH - Downstream Manhole, Survey Begins - 29 0273252.5 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (13)

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    22.9 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    34.3 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

    52.7 ft. - Crack Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Roots Fine Barrell, from 02 to 04 o'clock - COMING FROM CRACK

    85.7 ft. - Roots Fine Barrell, from 02 to 04 o'clock - COMING FROM CRACK

  • Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    85.7 ft. - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    103.7 ft. - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    144.2 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    175.3 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"

    187.2 ft. - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    196.4 ft. - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Roots Fine Barrell, from 09 to 10 o'clock

    196.4 ft. - Roots Fine Barrell, from 09 to 10 o'clock

  • Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"

    241.1 ft. - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"

  • Joint Offset Medium

    250.3 ft. - Joint Offset Medium

Observations (31)

DistanceCodeObservation
241.1TBA
187.2TBA
0MWM
0AMH29 0273
154.4TB
22.9CM
85.1TFC
171.9TF
103.7CM
6.5TF
144.2TB
87.6TF
196.4CM
0MWL
52.7CM
3.9TFC
130.3TB
250.3JOM
252.2TF
126.8TFC
166TFC
34.3CL
45.9TF
196.4RFB
252.5AMH29 0274
175.3CL
85.7RFBCOMING FROM CRACK
100.6TF
85.7CM
247.3TFC
249.9TFC

Properties (4)

additional_info
SC306892
custom_field_two
3
customer
LACSD
datetime