Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 1, 2016, 10:08 AM
Date
04/01/2016
W/O
563385
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00083
PipeID
P08792
Time
3:08 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3303
Sewer Name
B JOINT OUTFALL B - UNIT 1J
City
SAN GABRIEL
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
21
Purpose
Routine Assessment
Project
WO_563385_TV15176_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
B 0302
Downstream MH
B 0536
Dir. of Survey
Upstream
Length Surveyed
481 ft.
Total Length
481 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2R00
O&M Rating
190
Overall Index
2
Overall Quick
Overall Rating
192
Pipe schematic from manhole B 0302 to B 0536
MH: B 0302MH: B 0536upstream0 ft. AMH - Upstream Manhole, Survey Ends - B 05360.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 10 O'CLOCK3 ft. MGO - General Observation - COCKROACHES IN MANHOLE3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish14.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"49.2 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES74.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"104.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"162 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"175.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"232.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"274.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"372.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"476.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"479 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start481 ft. MWM - Water Mark, 35 %of cross sectional area481 ft. AMH - Downstream Manhole, Survey Begins - B 0302481 ft. MWL - Water Level, 20 %of cross sectional area481 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    431.8 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    478 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (19)

DistanceCodeObservation
305.8TF
2DAGS
0MWM
466.8TFA
4.2TFC
376.6TB
0AMHB 0302
478MGOCOCKROACHES IN MANHOLE
319TB
480.9MGOACTIVE CONNECTION AT MH 10 O'CLOCK
248.5TBA
0MWL
0MGOCOCKROACHES IN MANHOLE
478DAGS
431.8CL
108.9TFC
406.3TFA
206.1TFC
481AMHB 0536

Properties (4)

additional_info
SC305429
custom_field_two
4
customer
LACSD
datetime
2016-04-01T03:08:32-07:00