Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 18, 2017, 12:45 AM
  • H 0198_H 0197 _031417_111257.mp4

Date
02/17/2017
W/O
1590881
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00169
PipeID
P11222
Time
4:45 PM
Certificate
U-715-0700770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4321
Sewer Name
H JOINT OUTFALL H - UNIT 2C
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
WO_624328_TV02168_MAR2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
H 0198
Downstream MH
H 0197
Dir. of Survey
Downstream
Length Surveyed
405.3 ft.
Total Length
405.3 ft.
Structural Index
3
Structural Quick
3O2O
Structural Rating
403
O&M Index
2
O&M Quick
2O00
O&M Rating
160
Overall Index
2
Overall Quick
Overall Rating
563
Pipe schematic from manhole H 0198 to H 0197
MH: H 0198MH: H 0197downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 01980 ft. MWM - Water Mark, 30 %of cross sectional area4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start175 ft. SAP - Surface Aggregate Projecting, from 08 to 10 o'clock, within 8 inches of joint: NO405 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish405 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish405 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish405.3 ft. AMH - Downstream Manhole, Survey Ends - H 0197

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 10 o'clock, within 8 inches of joint: NO

    175 ft. - Surface Aggregate Projecting, from 08 to 10 o'clock, within 8 inches of joint: NO

Observations (11)

DistanceCodeObservation
405.3AMHH 0197
175SAP
405SSS
4DAGS
0MWL
405SAV
0AMHH 0198
0MWM
4SSS
4SAV
405DAGS

Properties (4)

additional_info
SC318735
custom_field_two
3
customer
LACSD
datetime
2017-02-17T16:45:05-08:00