Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 9, 2016, 10:57 AM
  • 02 1403_02 1402_20160509_043139.mp4

Date
05/09/2016
W/O
568667
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02974
Time
3:57 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3368
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_568667_TV02220_MAY2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Upstream MH
02 1403
Downstream MH
02 1402
Dir. of Survey
Downstream
Length Surveyed
734.5 ft.
Total Length
734.5 ft.
Structural Index
4
Structural Quick
5132
Structural Rating
11
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole 02 1403 to 02 1402
MH: 02 1403MH: 02 1402downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 14030 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start14.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start35.2 ft. SRP - Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start244.1 ft. LR - Alignment Right, 10 %695.7 ft. SRP - Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish727.6 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish728.7 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish734.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1402

Observation photos (4)

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    14.1 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    35.2 ft. - Surface Reinforcement Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Alignment Right, 10 %

    244.1 ft. - Alignment Right, 10 %

Observations (11)

DistanceCodeObservation
728.7SAV
14.1SAV
35.2SRP
244.1LR
2.1SRV
0MWM
0AMH02 1403
727.6SRV
734.5AMH02 1402
0MWL
695.7SRP

Properties (4)

additional_info
SC300366
custom_field_two
2
customer
LACSD
datetime
2016-05-09T03:57:47-07:00