Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 18, 2017, 07:32 AM
  • 02 1186_02 1185_18082017_003313.mpg

Date
08/18/2017
W/O
652007
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00262
PipeID
P03694
Time
12:32 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4788
Sewer Name
02 GARFIELD AVENUE DIVERSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
WO_652007_TV02291_AUG2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 1186
Downstream MH
02 1185
Dir. of Survey
Downstream
Length Surveyed
377.3 ft.
Total Length
377.3 ft.
Structural Index
2
Structural Quick
2111
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
3
Pipe schematic from manhole 02 1186 to 02 1185
MH: 02 1186MH: 02 1185downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 118614.8 ft. CS - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES267.9 ft. CC - Crack Circumferential, from 11 to 03 o'clock, within 8 inches of joint: YES377.3 ft. AMH - Downstream Manhole, Survey Ends - 02 1185

Observation photos (2)

  • Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

    14.8 ft. - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 11 to 03 o'clock, within 8 inches of joint: YES

    267.9 ft. - Crack Circumferential, from 11 to 03 o'clock, within 8 inches of joint: YES

Observations (6)

DistanceCodeObservation
0MWM
267.9CC
0MWL
377.3AMH02 1185
14.8CS
0AMH02 1186

Properties (4)

additional_info
SC345547
custom_field_two
4
customer
LACSD
datetime
2017-08-18T00:32:45-07:00