Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 4, 2017, 08:41 AM
  • 08 0477_08 0645 _04102017_014210.mp4

Date
10/04/2017
W/O
663253
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00025
PipeID
P20118
Time
1:41 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4284
Sewer Name
08 216TH STREET RELOCATION TRUNK
City
CARSON
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
WO_663253_TV08140_OCT2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
08 0477
Downstream MH
08 0645
Dir. of Survey
Downstream
Length Surveyed
23.4 ft.
Total Length
23.4 ft.
Structural Index
4
Structural Quick
5333
Structural Rating
24
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
24
Pipe schematic from manhole 08 0477 to 08 0645
MH: 08 0477MH: 08 0645downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 04770 ft. MWL - Water Level, 30 %of cross sectional area2.2 ft. MGO - General Observation - MAG COAT START2.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start18.9 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish18.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish18.9 ft. MGO - General Observation - MAG COAT FINISH23.4 ft. AMH - Downstream Manhole, Survey Ends - 08 0645

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    18.9 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (10)

DistanceCodeObservation
2.2MGOMAG COAT START
0MWM
18.9SRV
18.9SAV
0AMH08 0477
2.2SAV
0MWL
2.2SRV
18.9MGOMAG COAT FINISH
23.4AMH08 0645

Properties (4)

additional_info
SC352130
custom_field_two
1
customer
LACSD
datetime
2017-10-04T01:41:53-07:00