Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 17, 2017, 04:56 AM
  • 18 0891_18 0890 _20170516_230841.mp4

Date
05/16/2017
W/O
635479
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00709
PipeID
P14742
Time
9:56 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4498
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
WO_635479_TV18051_MAY2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
18 0891
Downstream MH
18 0890
Dir. of Survey
Downstream
Length Surveyed
658.2 ft.
Total Length
658.2 ft.
Structural Index
4
Structural Quick
5H3H
Structural Rating
369
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
369
Pipe schematic from manhole 18 0891 to 18 0890
MH: 18 0891MH: 18 0890downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 08910 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area10.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start54.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start73.6 ft. SRV - Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: YES87.4 ft. SRV - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO171.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish354.6 ft. SRV - Surface Reinforcement Visible, from 08 to 11 o'clock, within 8 inches of joint: NO386.3 ft. SRV - Surface Reinforcement Visible, from 12 to 04 o'clock, within 8 inches of joint: NO409.1 ft. SRV - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: NO441.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start441.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start649.5 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish658.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK658.2 ft. AMH - Downstream Manhole, Survey Ends - 18 0890658.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish658.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (9)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    54.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: YES

    73.6 ft. - Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO

    87.4 ft. - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 08 to 11 o'clock, within 8 inches of joint: NO

    354.6 ft. - Surface Reinforcement Visible, from 08 to 11 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 12 to 04 o'clock, within 8 inches of joint: NO

    386.3 ft. - Surface Reinforcement Visible, from 12 to 04 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: NO

    409.1 ft. - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    441.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    441.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
441.1SAP
10.9SSS
658.2MGOCONNECTION AT MH 3 O'CLOCK
649.5SRV
658.2AMH18 0890
658.2SSS
658.2SAP
0AMH18 0891
409.1SRV
171.6SAP
354.6SRV
54.1SAP
0MWL
0MWM
441.1SRV
87.4SRV
386.3SRV
73.6SRV

Properties (4)

additional_info
SC345307
custom_field_two
2
customer
LACSD
datetime
2017-05-16T21:56:14-07:00