Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 8, 2016, 06:20 AM
  • 02 0345_02 0344B _070716_232042.mp4

Date
07/07/2016
W/O
574757
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00259
PipeID
P02659
Time
11:20 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3562
Sewer Name
02 EAST COMPTON BOULEVARD RELIEF TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
33
Purpose
Routine Assessment
Project
WO_574757_TV02059_JUNE2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0345
Downstream MH
02 0344B
Dir. of Survey
Downstream
Length Surveyed
54.8 ft.
Total Length
54.8 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 02 0345 to 02 0344B
MH: 02 0345MH: 02 0344Bdownstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 034511.6 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES21.8 ft. CM - Crack Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES31.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start48.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish54.8 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK54.8 ft. AMH - Downstream Manhole, Survey Ends - 02 0344B

Observation photos (3)

  • Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    11.6 ft. - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

    21.8 ft. - Crack Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    31.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWL
48.2CM
54.8MGOCONNECTION AT THE MH 3 OC'LOCK
54.8AMH02 0344B
11.6CM
0MWM
0AMH02 0345
21.8CM
31.8CM

Properties (4)

additional_info
SC305868
custom_field_two
3
customer
LACSD
datetime
2016-07-07T23:20:24-07:00