Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 8, 2016, 06:10 AM
  • 02 0346_02 0345 _070716_231038.mp4

Date
07/07/2016
W/O
574757
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00259
PipeID
P02660
Time
11:10 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3562
Sewer Name
02 EAST COMPTON BOULEVARD RELIEF TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
33
Purpose
Routine Assessment
Project
WO_574757_TV02059_JUNE2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0346
Downstream MH
02 0345
Dir. of Survey
Downstream
Length Surveyed
296.5 ft.
Total Length
296.5 ft.
Structural Index
3
Structural Quick
3511
Structural Rating
16
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
16
Pipe schematic from manhole 02 0346 to 02 0345
MH: 02 0346MH: 02 0345downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 03460 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area6.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES12 ft. CM - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES29.8 ft. CM - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES64 ft. CM - Crack Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES80.5 ft. CC - Crack Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES84.4 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start289.9 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish296.5 ft. AMH - Downstream Manhole, Survey Ends - 02 0345

Observation photos (6)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    6.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

    12 ft. - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    29.8 ft. - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES

    64 ft. - Crack Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES

    80.5 ft. - Crack Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    84.4 ft. - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
64CM
29.8CM
296.5AMH02 0345
80.5CC
289.9CM
6.8CM
0AMH02 0346
0MGOCONNECTION AT THE MH 9 OC'LOCK
0MWL
0MWM
84.4CM
12CM

Properties (4)

additional_info
SC305868
custom_field_two
3
customer
LACSD
datetime
2016-07-07T23:10:22-07:00