Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 6, 2018, 10:21 AM
  • Section#2_08 0100_08 0099__962018__I0063.mp4

Date
09/06/2018
W/O
#
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00014
PipeID
P00127
Time
3:21 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0063
Sewer Name
08 MAIN STREET EXTENSION TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
01
Purpose
Capital Improvement Program Assesment
Project
20180906MDM_MAIN_STREET_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0100
Downstream MH
08 0099
Dir. of Survey
Downstream
Length Surveyed
392.8 ft.
Total Length
392.8 ft.
Structural Index
3
Structural Quick
413]
Structural Rating
745
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
747
Pipe schematic from manhole 08 0100 to 08 0099
MH: 08 0100MH: 08 0099downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - MH CONN 9:00 ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 3:30AM0 ft. MWL - Water Level, 10 %of cross sectional area8 ft. MGO - General Observation - 12" VCP10.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT13.4 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - HAIRLINE13.4 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H16.6 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H19.8 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL23.2 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL23.2 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SL23.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL25.5 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - H31.8 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS31.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT J0INTS31.8 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS31.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS34.6 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 03 to 05 o'clock, , within 8 inches of joint: YES - PAPER ON A WOOD STICK42 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB44.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB90.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB93.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB140.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB143.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB191.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB194.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB240.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB244.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB296.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6", 6" - STUB299.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB341.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB344.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB392.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - SLIGHT 25% AT JOINTS392.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE 60% AT JOINTS392.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 25% AT JOINTS392.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SLIGHT 40% AT JOINTS392.8 ft. AMH - Downstream Manhole, Survey Ends - 4:25AM

Observation photos (2)

  • General Observation - 12" VCP

    8 ft. - General Observation - 12" VCP

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

    10.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

Observations (38)

DistanceCodeObservation
25.5FLH
31.8FLHAIRLINE AT JOINTS
31.8FCHAIRLINE AT J0INTS
8MGO12" VCP
34.6DSZPAPER ON A WOOD STICK
10.5FMSLIGHT
194.9TFCSTUB
93.4TFCSTUB
13.4FLHAIRLINE
240.9TFCSTUB
140.4TFCSTUB
90.6TFCSTUB
31.8FLSLIGHT AT JOINTS
23.2FCSL
0MWM
0MGOMH CONN 9:00 ACTIVE
392.2FLSLIGHT 25% AT JOINTS
244.6TFCSTUB
42TFCSTUB
299.3TBSTUB
296.2TBSTUB
19.8FCSL
23.2FLSL
0AMH3:30AM
392.2FCHAIRLINE 60% AT JOINTS
31.8FCSLIGHT AT JOINTS
392.8AMH4:25AM
392.2FL25% AT JOINTS
341.9TFCSTUB
0MWL
13.4FLH
23.2FLSL
191.7TFCSTUB
143.2TFCSTUB
392.2FCSLIGHT 40% AT JOINTS
44.7TFSTUB
344.7TFSTUB
16.6FCH

Properties (4)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2018-09-06T03:21:02-07:00