Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 29, 2018, 06:51 PM
  • 02 0911_02 0910_8292018_115917.mp4

Date
08/29/2018
W/O
PENDING
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00252
PipeID
P03479
Time
11:51 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0963
Sewer Name
02 DOWNEY-BELLFLOWER DIVERSION TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
20180829SHO_DOWNEY_BELLFLOWER_DIVERSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
02 0911
Downstream MH
02 0910
Dir. of Survey
Downstream
Length Surveyed
382.1 ft.
Total Length
382.1 ft.
Structural Index
3
Structural Quick
3A27
Structural Rating
47
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
47
Pipe schematic from manhole 02 0911 to 02 0910
MH: 02 0911MH: 02 0910downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - MH 09110 ft. MWM - Water Mark, 30 %of cross sectional area6.4 ft. CS - Crack Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES8 ft. CS - Crack Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES, Start13.9 ft. CS - Crack Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES, Finish14 ft. FS - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES14 ft. MGP - General Photograph18.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start24.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish64.6 ft. FS - Fracture Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES70.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES99 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start108.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish144.7 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start150.3 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Finish174 ft. CS - Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES176.7 ft. FS - Fracture Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES201.9 ft. FS - Fracture Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES212.4 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES231.4 ft. FS - Fracture Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES236.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start243.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish247.6 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - JOINT TO JOINT263.5 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES272.2 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES - JOINT TO JOINT373.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES - JOINT TO JOINT382.1 ft. AMH - Downstream Manhole, Survey Ends - MH 0910

Observation photos (10)

  • Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    14 ft. - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

  • General Photograph

    14 ft. - General Photograph

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    18.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES

    64.6 ft. - Fracture Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    99 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

    174 ft. - Crack Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES

    176.7 ft. - Fracture Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES

    201.9 ft. - Fracture Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    236.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Downstream Manhole, Survey Ends - MH 0910

    382.1 ft. - Downstream Manhole, Survey Ends - MH 0910

Observations (28)

DistanceCodeObservation
243.5FL
14FS
263.5FL
6.4CS
201.9FS
13.9CS
212.4FL
373.9CLJOINT TO JOINT
174CS
99FL
24.4FL
108.2FL
14MGP
144.7CL
18.5FL
247.6FLJOINT TO JOINT
176.7FS
236.8FL
8CS
150.3CL
382.1AMHMH 0910
64.6FS
272.2CLJOINT TO JOINT
0MWL
231.4FS
0AMHMH 0911
70.1CL
0MWM

Properties (4)

custom_field_three
JOINT TO JOINT CRACKS & FRACTURES
custom_field_two
2
customer