Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 20, 2018, 08:05 PM
  • Section#2_02 1880_02 1879__8202018__I0057.mp4

Date
08/20/2018
W/O
PENDING
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00246
PipeID
P04238
Time
1:05 PM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0057
Sewer Name
02 DOUGLAS AVENUE TRUNK
City
EAST LA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
20180820SHO_DOUGLAS_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
02 1880
Downstream MH
02 1879
Dir. of Survey
Downstream
Length Surveyed
325.2 ft.
Total Length
325.2 ft.
Structural Index
3
Structural Quick
413K
Structural Rating
194
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
194
Pipe schematic from manhole 02 1880 to 02 1879
MH: 02 1880MH: 02 1879downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - MH 18800 ft. MWM - Water Mark, 15 %of cross sectional area4.6 ft. JOL - Joint Offset Large4.6 ft. B - Broken, from 04 to 05 o'clock, within 8 inches of joint: YES10.9 ft. JOL - Joint Offset Large11.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start31.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"76.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"116.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"180.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"197.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"241.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"284.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"319.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.2 ft. AMH - Downstream Manhole, Survey Ends - MH 1879

Observation photos (4)

  • Joint Offset Large

    4.6 ft. - Joint Offset Large

  • Broken, from 04 to 05 o'clock, within 8 inches of joint: YES

    4.6 ft. - Broken, from 04 to 05 o'clock, within 8 inches of joint: YES

  • Joint Offset Large

    10.9 ft. - Joint Offset Large

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
180.1TF
4.6JOL
325.2AMHMH 1879
284.3TFA
0MWL
0AMHMH 1880
116.2TF
4.6B
319.1CM
31.7TFC
10.9JOL
76.3TF
11.5CM
0MWM
241.3TF
197.5TF

Properties (4)

custom_field_three
BROKEN PIPE & OFFSET JOINTS
custom_field_two
2
customer
LACSD
datetime
2018-08-20T13:05:22-07:00