Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 20, 2018, 08:24 AM
  • 01 1116_01 1115_8202018_014838.mp4

Date
08/20/2018
W/O
0723688
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00210
PipeID
P01967
Time
1:24 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0952
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTING PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
20180820MDM_HUNTINGTON_PARK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
01 1116
Downstream MH
01 1115
Dir. of Survey
Downstream
Length Surveyed
190.5 ft.
Total Length
190.5 ft.
Structural Index
3
Structural Quick
3726
Structural Rating
33
O&M Index
4
O&M Quick
4200
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
41
Pipe schematic from manhole 01 1116 to 01 1115
MH: 01 1116MH: 01 1115downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:45AM8 ft. MGO - General Observation - 18" VCP23.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open37.7 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - HAIRLINE44.8 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H53.4 ft. MWM - Water Mark, 60 %of cross sectional area70.1 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H71 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open74.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open114 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - H124.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open126 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open132.1 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H137.4 ft. FC - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - H142.5 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H145.2 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H145.2 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H155.5 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H158.2 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - SL171.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active173.9 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H177.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open179 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SL190 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active190.5 ft. AMH - Downstream Manhole, Survey Ends - 2:10AM

Observation photos (1)

  • General Observation - 18" VCP

    8 ft. - General Observation - 18" VCP

Observations (27)

DistanceCodeObservation
155.5FLH
53.4MWM
177.3TFOpen
70.1FCH
137.4FCH
126TFOpen
71TFOpen
142.5FCH
0MWL
114FLH
145.2FLH
190.5AMH2:10AM
190MGOConn. @ Mh, 9 O' Clock. Active
0MWM
23.7TFOpen
132.1FCH
74.3TFOpen
145.2FLH
158.2FCSL
44.8FCH
8MGO18" VCP
173.9FLH
37.7FLHAIRLINE
171.7TFActive
0AMH1:45AM
124.2TFOpen
179FLSL

Properties (4)

custom_field_three
SLIGHT & HAIRLINE FRACTURES
custom_field_two
4
customer
LACSD
datetime
2018-08-20T01:24:59-07:00