Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2018, 12:46 PM
  • 01 1105_01 1104_8242018_054943.mp4

Date
08/24/2018
W/O
0723688
Weather
Dry
Operator/Surveyor
Reveles
Sewer ID
Z00210
PipeID
P01955
Time
5:46 AM
Certificate
U-115-06022633
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0954
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTINGTON PARK TRUNK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
08242018ROIII_Huntington_Park_Trunk
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
01 1105
Downstream MH
01 1104
Dir. of Survey
Downstream
Length Surveyed
303.9 ft.
Total Length
303.9 ft.
Structural Index
2
Structural Quick
5141
Structural Rating
78
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
86
Pipe schematic from manhole 01 1105 to 01 1104
MH: 01 1105MH: 01 1104downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 12"0 ft. AMH - Upstream Manhole, Survey Begins - 05:50 AM1.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: YES, Start1.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES, Start13.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"49.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 4"86.8 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES101.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - Open102.2 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES117.5 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES120.7 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES135.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES146 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES150 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 4"169.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES179.3 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES180.9 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 0" - Open181.9 ft. CC - Crack Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES184.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES187 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES189.2 ft. CM - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES205 ft. CM - Crack Multiple, from 01 to 02 o'clock, within 8 inches of joint: YES210 ft. CH3 - Crack Longitudinal Hinge, 3, from 09 to 03 o'clock, within 8 inches of joint: YES212.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES217.9 ft. CH2 - Crack Longitudinal Hinge, 2, from 10 to 02 o'clock, within 8 inches of joint: YES220.5 ft. MWL - Water Level, 15 %of cross sectional area220.5 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES225.2 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES228.3 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES230.5 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES235.6 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES238.3 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES241.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES256.7 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES260.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: YES, Finish260.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES, Finish260.3 ft. MWL - Water Level, 30 %of cross sectional area274.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES275.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES276.7 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES279.5 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES281.7 ft. CM - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES284.6 ft. CM - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES287.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES287.1 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES289.3 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES297.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES303.9 ft. AMH - Downstream Manhole, Survey Ends - 06:38 AM303.9 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 12"

Observations (51)

DistanceCodeObservation
1.4DAGS
289.3CM
135.6CL
279.5FL
0MWL
0MWM
235.6CL
169.5CL
101.4TFOpen
284.6CM
0TFA
281.7CM
287.1CL
220.5MWL
238.3CL
276.7CL
260.3DAGS
102.2CL
230.5CL
274.1CL
179.3CL
260.3DAGS
180.9TFOpen
1.3DAGS
275.3CL
303.9AMH06:38 AM
146CL
303.9TFA
205CM
256.7CL
189.2CM
181.9CC
187CL
120.7CL
241.1CL
86.8CL
117.5CL
297.1CL
260.3MWL
212.3CL
210CH3
217.9CH2
150TFA
13.1TFC
0AMH05:50 AM
228.3CL
220.5CL
225.2CL
184.3CL
287.1CL
49.4TFC

Properties (3)

custom_field_two
2
customer
LACSD
datetime