Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 25, 2017, 09:56 AM
  • 29 0005_29 0004 _20170525_031120.mp4

Date
05/25/2017
W/O
635600
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00849
PipeID
P17679
Time
2:56 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4609
Sewer Name
29 SIGNAL HILL OUTFALL TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
19
Purpose
Routine Assessment
Project
WO_635600_TV29096_MAY2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
29 0005
Downstream MH
29 0004
Dir. of Survey
Downstream
Length Surveyed
93.2 ft.
Total Length
93.2 ft.
Structural Index
3
Structural Quick
5C3C
Structural Rating
180
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
180
Pipe schematic from manhole 29 0005 to 29 0004
MH: 29 0005MH: 29 0004downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 00052.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start19.3 ft. IS - Infiltration Stain, from 01 to 04 o'clock, within 8 inches of joint: YES59.4 ft. IS - Infiltration Stain, from 01 to 04 o'clock, within 8 inches of joint: YES, Start93.1 ft. IS - Infiltration Stain, from 01 to 04 o'clock, within 8 inches of joint: YES, Finish93.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish93.2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish93.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish93.2 ft. AMH - Downstream Manhole, Survey Ends - 29 0004

Observation photos (5)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Stain, from 01 to 04 o'clock, within 8 inches of joint: YES

    19.3 ft. - Infiltration Stain, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, from 01 to 04 o'clock, within 8 inches of joint: YES, Start

    59.4 ft. - Infiltration Stain, from 01 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0MWM
19.3IS
93.2SRV
93.2SAP
59.4IS
4.2SRV
2.1SSS
0MWL
93.1IS
0AMH29 0005
93.2AMH29 0004
2.6SAP
93.1SSS

Properties (4)

additional_info
SC345319
custom_field_two
2
customer
LACSD
datetime