Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 3, 2018, 08:25 AM
  • 01 0240_01 0239_03082018_014215.mp4

Date
08/03/2018
W/O
717715
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00218
PipeID
P01285
Time
1:25 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5965
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
WO_717715_TV01205_AUG2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0240
Downstream MH
01 0239
Dir. of Survey
Downstream
Length Surveyed
302.8 ft.
Total Length
302.8 ft.
Structural Index
3
Structural Quick
4D3F
Structural Rating
204
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
204
Pipe schematic from manhole 01 0240 to 01 0239
MH: 01 0240MH: 01 0239downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CAPPED LATERAL 9 O'CLOCK @ MH0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CAPPED LATERAL 3 O'CLOCK @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 01 024019.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start32.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"32.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"86.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"95.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"103.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES137.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"167.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES184.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"188.9 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES197.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish197.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start208.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"235.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"237.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"273.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"273.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"282.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"285.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"302.7 ft. MGO - General Observation - CAPPED LATERAL 9 O'CLOCK @ MH302.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish302.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0239

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    19.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    103.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    167.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    188.9 ft. - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    197.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (28)

DistanceCodeObservation
273.3TB
184.5TFC
197.6CM
197.6FM
282.3TB
285.3TFC
302.7MGOCAPPED LATERAL 9 O'CLOCK @ MH
0MWL
140.1TF
235.2TF
137.9TFC
19.1CM
237.8TFC
167.9FM
188.9FM
0MGOCAPPED LATERAL 9 O'CLOCK @ MH
95.6TF
32.1TFC
86.9TFC
0MWM
302.8AMH01 0239
273.3TF
32.1TB
302.7FM
0MGOCAPPED LATERAL 3 O'CLOCK @ MH
103.1FM
208.7TF
0AMH01 0240

Properties (4)

additional_info
SC364728
custom_field_two
2
customer
LACSD
datetime
2018-08-03T01:25:35-07:00