Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 2, 2018, 10:58 AM
  • 01 0247_01 0246_02082018_040830.mp4

Date
08/02/2018
W/O
717715
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00218
PipeID
P01292
Time
3:58 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5963
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
WO_717715_TV01205_AUG2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0247
Downstream MH
01 0246
Dir. of Survey
Downstream
Length Surveyed
328.6 ft.
Total Length
328.6 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
195
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
195
Pipe schematic from manhole 01 0247 to 01 0246
MH: 01 0247MH: 01 0246downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02470 ft. MWM - Water Mark, 20 %of cross sectional area2.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start61.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"100.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"154.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"208.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"249.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"275.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"328.6 ft. AMH - Downstream Manhole, Survey Ends - 01 0246328.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish328.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK328.6 ft. MGO - General Observation - CONNECTION AT MH 12 O'CLOCK

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
249.4TFC
154.6TFC
328.6AMH01 0246
328.6CM
275.8TFC
0MWL
100.4TFC
328.6MGOCONNECTION AT MH 3 O'CLOCK
2.5CM
0AMH01 0247
61.8TFC
0MWM
208.3TF
328.6MGOCONNECTION AT MH 12 O'CLOCK

Properties (4)

additional_info
SC364726
custom_field_two
3
customer
LACSD
datetime
2018-08-02T03:58:38-07:00