Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 3, 2018, 10:07 AM
  • 01 0264_01 0263_03082018_032349.mp4

Date
08/03/2018
W/O
717715
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00218
PipeID
P01310
Time
3:07 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5965
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_717715_TV01205_AUG2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0264
Downstream MH
01 0263
Dir. of Survey
Downstream
Length Surveyed
331.8 ft.
Total Length
331.8 ft.
Structural Index
4
Structural Quick
4L00
Structural Rating
264
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
264
Pipe schematic from manhole 01 0264 to 01 0263
MH: 01 0264MH: 01 0263downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02643.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.3 ft. MGO - General Observation - ABANDONED MH88.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"109.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"151.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"178.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"193.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"238.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"271.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"331.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0263331.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish331.8 ft. MGO - General Observation - CAPPED LATERAL 9 O'CLOCK @ MH331.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
0MGOCONNECTION AT MH 3 O'CLOCK
331.8AMH01 0263
88.6TFC
0MWM
0MWL
331.8FM
271.4TF
0AMH01 0264
238.5TFC
151.7TF
193.7TF
331.8MGOCAPPED LATERAL 9 O'CLOCK @ MH
178.5TF
331.8MGOCONNECTION AT MH 3 O'CLOCK
3.6FM
7.3MGOABANDONED MH
109.5TF

Properties (4)

additional_info
SC364728
custom_field_two
2
customer
LACSD
datetime