Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 9, 2018, 06:08 AM
  • 18 0676_18 0675 _08082018_232005.mp4

Date
08/08/2018
W/O
718121
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00696
PipeID
P14525
Time
11:08 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5975
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
WO_718121_TV18169_AUG2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0676
Downstream MH
18 0675
Dir. of Survey
Downstream
Length Surveyed
325.3 ft.
Total Length
325.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
2
Overall Quick
Overall Rating
128
Pipe schematic from manhole 18 0676 to 18 0675
MH: 18 0676MH: 18 0675downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 06760 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area3.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start100.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"104.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"204.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"305.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"325.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0675325.3 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (1)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES, Start

    3.1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
325.3AMH18 0675
3.1DAE
204.8TF
100.3TB
0AMH18 0676
0MWM
104.7TFC
305.5TFC
0MWL
325.3DAE

Properties (4)

additional_info
SC364739
custom_field_two
3
customer
LACSD
datetime
2018-08-08T23:08:11-07:00