- Date
- 08/09/2018
- W/O
- 718121
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00696
- PipeID
- P14511
- Time
- 1:14 AM
- Certificate
- U-508-7069
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K5975
- Sewer Name
- 18 PHOEBE AVENUE TRUNK
- City
- LA MIRADA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 36
- Purpose
- Routine Assessment
- Project
- WO_718121_TV18169_AUG2018
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 24 in.
- Width
- 24 in.
- Upstream MH
- 18 0662
- Downstream MH
- 18 0661
- Dir. of Survey
- Downstream
- Length Surveyed
- 299.7 ft.
- Total Length
- 299.7 ft.
- Structural Index
- 3
- Structural Quick
- 3A24
- Structural Rating
- 44
- O&M Index
- 2
- O&M Quick
- 2K00
- O&M Rating
- 118
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 162
Pipe schematic from manhole 18 0662 to 18 0661 Observation photos (6)

2.7 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

36.5 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

61.7 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

122.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

211.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

232.1 ft. - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES, Start