Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 7, 2018, 09:15 AM
  • 01 0217_01 0216_07082018_023653.mp4

Date
08/07/2018
W/O
717798
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01259
Time
2:15 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5971
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
WO_717798_TV01222_AUG2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
01 0217
Downstream MH
01 0216
Dir. of Survey
Downstream
Length Surveyed
381.3 ft.
Total Length
381.3 ft.
Structural Index
3
Structural Quick
4E3N
Structural Rating
357
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
357
Pipe schematic from manhole 01 0217 to 01 0216
MH: 01 0217MH: 01 0216downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02170 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK3.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.1 ft. FM - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES29.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"69.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"86.4 ft. FM - Fracture Multiple, from 07 to 03 o'clock, within 8 inches of joint: YES90.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"125.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"152.9 ft. CC - Crack Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES153.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"209.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"216.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES224.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"225.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES231.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"233.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start259.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"293.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"313.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"354 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"375.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish381.3 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK381.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish381.3 ft. AMH - Downstream Manhole, Survey Ends - 01 0216

Observation photos (7)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    3.1 ft. - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 03 o'clock, within 8 inches of joint: YES

    86.4 ft. - Fracture Multiple, from 07 to 03 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES

    152.9 ft. - Crack Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    216.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    225.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    233.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (28)

DistanceCodeObservation
90.1TF
3.1SAV
153.7TF
0MWL
0AMH01 0217
259.8TF
293.1TF
224.4TF
231.9TF
0MWM
29.1TF
0MGOCONNECTION AT MH 9 O'CLOCK
216.5FM
381.3MGOCONNECTION AT MH 9 O'CLOCK
0MGOCONNECTION AT MH 3 O'CLOCK
209.6TF
381.3SAV
233.2FM
225.8FM
86.4FM
125.7TF
354TF
381.3AMH01 0216
313.3TF
69.5TF
152.9CC
375.2FM
3.1FM

Properties (4)

additional_info
SC364734
custom_field_two
2
customer
LACSD
datetime
2018-08-07T02:15:22-07:00