Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 7, 2018, 09:38 AM
  • 01 0216_01 0215_07082018_025656.mp4

Date
08/07/2018
W/O
717798
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01258
Time
2:38 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5971
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
WO_717798_TV01222_AUG2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
01 0216
Downstream MH
01 0215
Dir. of Survey
Downstream
Length Surveyed
380.7 ft.
Total Length
380.7 ft.
Structural Index
3
Structural Quick
4M3N
Structural Rating
500
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
501
Pipe schematic from manhole 01 0216 to 01 0215
MH: 01 0216MH: 01 0215downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02162.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start34.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"80.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"87.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"136.5 ft. RFL - Roots Fine Lateral, at 02 o'clock136.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"159 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"230.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"270.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"276 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"298.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"323.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"329.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"339.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish351.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"358 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES366.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"380.7 ft. AMH - Downstream Manhole, Survey Ends - 01 0215380.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK380.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    358 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
270.9TF
230.2TF
351.4TF
159TF
87.9TF
136.5RFL
0MWM
2.5SAV
339.1FM
323.7TFC
298.4TF
329.1TF
366.9TF
380.7AMH01 0215
0MGOCONNECTION AT MH 9 O'CLOCK
380.7MGOCONNECTION AT MH 9 O'CLOCK
358FM
3.3FM
34.7TF
380.7SAV
128.3TF
0MWL
136.5TF
80.4TF
0AMH01 0216
276TF

Properties (4)

additional_info
SC364734
custom_field_two
2
customer
LACSD
datetime
2018-08-07T02:38:34-07:00