Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 7, 2018, 08:46 AM
  • 18 0619_18 0618 _07062018_020100.mp4

Date
06/07/2018
W/O
707100
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00692
PipeID
P14469
Time
1:46 AM
Certificate
U-0817-07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5642
Sewer Name
18 NORTH PLANT OUTFALL RELIEF TRUNK
City
WHITTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_707100_TV18033_JUN2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
18 0619
Downstream MH
18 0618
Dir. of Survey
Downstream
Length Surveyed
302.5 ft.
Total Length
302.5 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 18 0619 to 18 0618
MH: 18 0619MH: 18 0618downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 06192.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start51.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6"107.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start107.3 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish141.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6"280 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6"301.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish302.5 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK302.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0618

Observation photos (2)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    107.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

Observations (12)

DistanceCodeObservation
0MWL
301.1SAP
141.6TF
280TF
107.3SAP
302.5MGOCONNECTION AT MH 9 OCLOCK
51.9TF
302.5AMH18 0618
0MWM
107.3SRV
2.1SRV
0AMH18 0619

Properties (4)

additional_info
SC359197
custom_field_two
2
customer
LACSD
datetime
2018-06-07T01:46:38-07:00