Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 27, 2018, 06:41 AM
  • 08 0347A_08 0347 _26072018_234711.mp4

Date
07/26/2018
W/O
717825
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00003
PipeID
P00397
Time
11:41 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5799
Sewer Name
08 DAVIDSON CITY TRUNK, SECTS 1,2,&3
City
CARSON
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
15
Purpose
Routine Assessment
Project
WO_717825_TV08001_AUG2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
08 0347
Downstream MH
08 0347A
Dir. of Survey
Upstream
Length Surveyed
46.1 ft.
Total Length
46.1 ft.
Structural Index
3
Structural Quick
3824
Structural Rating
32
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
32
Pipe schematic from manhole 08 0347 to 08 0347A
MH: 08 0347MH: 08 0347Aupstream0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0.1 ft. AMH - Upstream Manhole, Survey Ends - 08 0347A21.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish21.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start21.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start43.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start46.1 ft. AMH - Downstream Manhole, Survey Begins - 08 034746.1 ft. MWM - Water Mark, 25 %of cross sectional area46.1 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    24.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    24.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0AMH08 0347
2.2SAV
24.2SAV
46.1SSS
0MWM
0MWL
24.2SSS
24.2SAP
46.1SAP
46AMH08 0347A
46.1MGOCONNECTION AT MH 3 O'CLOCK

Properties (4)

additional_info
SC364711
custom_field_two
2
customer
LACSD
datetime
2018-07-26T23:41:47-07:00