Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 24, 2018, 08:11 AM
  • 08 0375_08 0374 _24072018_011933.mp4

Date
07/24/2018
W/O
717825
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00003
PipeID
P00427
Time
1:11 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5792
Sewer Name
08 DAVIDSON CITY TRUNK, SECTS 1,2,&3
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
12
Purpose
Routine Assessment
Project
WO_717825_TV08001_AUG2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
08 0375
Downstream MH
08 0374
Dir. of Survey
Downstream
Length Surveyed
149.1 ft.
Total Length
149.1 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
87
O&M Index
1
O&M Quick
1D00
O&M Rating
23
Overall Index
2
Overall Quick
Overall Rating
110
Pipe schematic from manhole 08 0375 to 08 0374
MH: 08 0375MH: 08 0374downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 08 03750 ft. MWL - Water Level, 10 %of cross sectional area4 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start18.1 ft. RFJ - Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YES23.2 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40.5 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish40.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"53.8 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start68 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"92.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"100.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"125 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"142.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"149.1 ft. AMH - Downstream Manhole, Survey Ends - 08 0374149.1 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish149.1 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish149.1 ft. MGO - General Observation - CAPPED LATERAL 9 O'CLOCK @ MH

Observation photos (3)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    4 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    23.2 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    53.8 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
40.5RFJ
23.2RFJ
0MWM
149.1AMH08 0374
149.1SAV
40.5TFC
149.1RFJ
53.8RFJ
92.3TFC
4SAV
125TFC
68TFC
18.1RFJ
100.7TF
142.8TFC
0MGOCONNECTION AT MH 9 O'CLOCK
0AMH08 0375
149.1MGOCAPPED LATERAL 9 O'CLOCK @ MH
0MWL

Properties (4)

additional_info
SC364703
custom_field_two
3
customer
LACSD
datetime
2018-07-24T01:11:58-07:00