Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 2, 2018, 10:55 AM
  • 15 1088_15 1087_02052018_040935.mp4

Date
05/02/2018
W/O
696294
Weather
Light Rain
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00614
PipeID
P12848
Time
3:55 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5584
Sewer Name
15 MERCED TRUNK, SECTION 1
City
SOUTH EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
WO_696294_TV15099_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 1088
Downstream MH
15 1087
Dir. of Survey
Downstream
Length Surveyed
352.9 ft.
Total Length
352.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
140
Pipe schematic from manhole 15 1088 to 15 1087
MH: 15 1088MH: 15 1087downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 10882 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start30.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"79.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"131 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"179.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"231.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"282.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"331.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"351.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish352.9 ft. AMH - Downstream Manhole, Survey Ends - 15 1087352.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
2DAGS
231.2TFA
352.9AMH15 1087
0MGOCOCKROACHES IN MANHOLE
131TFA
0MWM
79.1TFA
0MWL
30.9TFA
282.7TFA
0AMH15 1088
179.4TFA
331.1TFC
351.5DAGS
352.9MGOCOCKROACHES IN MANHOLE

Properties (4)

additional_info
SC358545
custom_field_two
3
customer
LACSD
datetime
2018-05-02T03:55:35-07:00