- Date
- 08/01/2018
- W/O
- 717986
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00891
- PipeID
- P24944
- Time
- 11:25 PM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K5887
- Sewer Name
- 32 VALENCIA TRUNK
- City
- SANTA CLARITA
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 32
- Page No.
- 13
- Purpose
- Routine Assessment
- Project
- WO_717986_TV32059_AUG2018
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 24 in.
- Width
- 24 in.
- Upstream MH
- 32 0224
- Downstream MH
- 32 0223A
- Dir. of Survey
- Downstream
- Length Surveyed
- 113.1 ft.
- Total Length
- 113.1 ft.
- Structural Index
- 3
- Structural Quick
- 4221
- Structural Rating
- 10
- O&M Index
- 2
- O&M Quick
- 412C
- O&M Rating
- 48
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 58
Pipe schematic from manhole 32 0224 to 32 0223A Observation photos (4)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

65.4 ft. - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

91.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

109.2 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES