Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 27, 2018, 09:29 AM
  • 32 1165_32 1164_27072018_023913.mp4

Date
07/27/2018
W/O
717961
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00839
PipeID
P19619
Time
2:29 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5882
Sewer Name
32 SAN FERNANDO ROAD TRUNK
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
WO_717961_TV32021_AUG2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 1164
Downstream MH
32 1165
Dir. of Survey
Upstream
Length Surveyed
281.3 ft.
Total Length
281.3 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
168
O&M Index
2
O&M Quick
2J00
O&M Rating
112
Overall Index
3
Overall Quick
Overall Rating
280
Pipe schematic from manhole 32 1164 to 32 1165
MH: 32 1164MH: 32 1165upstream0 ft. AMH - Upstream Manhole, Survey Ends - 32 11650 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK1.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish1.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish220.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"279.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start279.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start281.3 ft. MWM - Water Mark, 25 %of cross sectional area281.3 ft. MWL - Water Level, 10 %of cross sectional area281.3 ft. AMH - Downstream Manhole, Survey Begins - 32 1164

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0MWM
0MWL
60.4TFC
279.8DAGS
281.3AMH32 1165
2SAP
279.8SAP
0AMH32 1164
281.3MGOACTIVE CONNECTION AT MH 3 O'CLOCK
2DAGS

Properties (4)

additional_info
SC359750
custom_field_two
2
customer
LACSD
datetime
2018-07-27T02:29:05-07:00