Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 31, 2018, 04:58 AM
  • F 0149_F 0148 _30072018_223343.mp4

Date
07/30/2018
W/O
717866
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00037
PipeID
P10181
Time
9:58 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5801
Sewer Name
F JOINT OUTFALL F - UNIT 3B
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39A
Purpose
Routine Assessment
Project
WO_717866_TV02231_AUG2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Width
63 in.
Upstream MH
F 0149
Downstream MH
F 0148
Dir. of Survey
Downstream
Length Surveyed
545.5 ft.
Total Length
545.5 ft.
Structural Index
3
Structural Quick
5D3U
Structural Rating
439
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
439
Pipe schematic from manhole F 0149 to F 0148
MH: F 0149MH: F 0148downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 01496.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start30.9 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start104.2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish504.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start543.4 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish545.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish545.5 ft. AMH - Downstream Manhole, Survey Ends - F 0148

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    30.9 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    504.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
543.4SRV
6.2SAP
504.1SRV
545.5SAP
30.9SRV
0MWM
0MWL
0AMHF 0149
104.2SRV
545.5AMHF 0148

Properties (4)

additional_info
364714
custom_field_two
2
customer
LACSD
datetime
2018-07-30T21:58:12-07:00