Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 8, 2018, 09:06 AM
  • B 0477_B 0476 _08062018_022114.mp4

Date
06/08/2018
W/O
706863
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00094
PipeID
P09002
Time
2:06 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5691
Sewer Name
B JOINT OUTFALL B - UNIT 5D
City
PASADENA
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
06
Purpose
Routine Assessment
Project
WO_706863_TV16037_JUN2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
B 0477
Downstream MH
B 0476
Dir. of Survey
Downstream
Length Surveyed
264.4 ft.
Total Length
264.4 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
4132
O&M Rating
13
Overall Index
2
Overall Quick
Overall Rating
18
Pipe schematic from manhole B 0477 to B 0476
MH: B 0477MH: B 0476downstream0 ft. MGO - General Observation - CONNECTION AT MH 6 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 04772.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start27.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"29.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"37 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"44.1 ft. RMC - Roots Medium Connection, at 09 o'clock, 20 %, within 8 inches of joint: NO44.1 ft. RBL - Roots Ball Lateral, at 10 o'clock, 85 %44.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"87.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"90.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"96.3 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES99.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"125.1 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES142 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"142 ft. RFC - Roots Fine Connection, at 09 o'clock145.8 ft. RFJ - Roots Fine Joint, from 09 to 12 o'clock, within 8 inches of joint: YES148.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"154.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"158 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"179.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"190.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"195.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"241.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"250 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"250 ft. RML - Roots Medium Lateral, at 10 o'clock, 40 %, within 8 inches of joint: NO264.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish264.4 ft. AMH - Downstream Manhole, Survey Ends - B 0476264.4 ft. MGO - General Observation - CONNECTION AT MH 12 O'CLOCK

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Connection, at 09 o'clock, 20 %, within 8 inches of joint: NO

    44.1 ft. - Roots Medium Connection, at 09 o'clock, 20 %, within 8 inches of joint: NO

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    125.1 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 09 to 12 o'clock, within 8 inches of joint: YES

    145.8 ft. - Roots Fine Joint, from 09 to 12 o'clock, within 8 inches of joint: YES

Observations (32)

DistanceCodeObservation
154.9TF
0MGOCONNECTION AT MH 6 O'CLOCK
2.1SAV
250TF
87.4TFC
44.1RMC
37TF
264.4SAV
29.8TFC
148.1TFC
44.1RBL
96.3RFJ
190.4TF
90.5TFC
0MGOCONNECTION AT MH 9 O'CLOCK
99.5TF
44.1TF
179.4TF
158TFC
264.4AMHB 0476
27.1TFC
145.8RFJ
142TF
142RFC
250RML
0MWM
0MWL
195.9TFC
125.1CL
264.4MGOCONNECTION AT MH 12 O'CLOCK
0AMHB 0477
241.3TF

Properties (4)

additional_info
SC359350
custom_field_two
3
customer
LACSD
datetime
2018-06-08T02:06:46-07:00