Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 8, 2018, 06:39 AM
  • B 0474_B 0473A_07062018_235139.mp4

Date
06/07/2018
W/O
706863
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00094
PipeID
P26504
Time
11:39 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5691
Sewer Name
B JOINT OUTFALL B - UNIT 5D
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
06
Purpose
Routine Assessment
Project
WO_706863_TV16037_JUN2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
B 0474
Downstream MH
B 0473A
Dir. of Survey
Downstream
Length Surveyed
230.1 ft.
Total Length
230.1 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
135
O&M Index
1
O&M Quick
1400
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
139
Pipe schematic from manhole B 0474 to B 0473A
MH: B 0474MH: B 0473Adownstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 04742.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.1 ft. RFJ - Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YES9.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish9.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start65.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"66.3 ft. RFJ - Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YES123.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"123.5 ft. RFL - Roots Fine Lateral, at 12 o'clock154.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"197.3 ft. RFC - Roots Fine Connection, at 02 o'clock197.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"230.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish230.1 ft. AMH - Downstream Manhole, Survey Ends - B 0473A

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
123.5TF
0MWM
2.1SAV
66.3RFJ
197.3RFC
3.1RFJ
9.1SAV
65.4TF
123.5RFL
0MGOCONNECTION AT MH 3 O'CLOCK
154.9TF
0MWL
9.1SAP
197.3TF
230.1SAP
0AMHB 0474
230.1AMHB 0473A

Properties (4)

additional_info
SC359350
custom_field_two
3
customer
LACSD
datetime
2018-06-07T23:39:06-07:00