Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 27, 2018, 08:02 AM
  • 08 0339_08 0338 _27072018_013330.mp4

Date
07/27/2018
W/O
717824
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00003
PipeID
P00389
Time
1:02 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5800
Sewer Name
08 DAVIDSON CITY TRUNK, SECTS 1,2,&3
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
14
Purpose
Routine Assessment
Project
WO_717824_TV08104_AUG2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
08 0339
Downstream MH
08 0338
Dir. of Survey
Downstream
Length Surveyed
350.2 ft.
Total Length
350.2 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
162
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
170
Pipe schematic from manhole 08 0339 to 08 0338
MH: 08 0339MH: 08 0338downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 03392.2 ft. MGO - General Observation - MAG COAT87.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start87.3 ft. SAP - Surface Aggregate Projecting, at 08 o'clock, within 8 inches of joint: YES240.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"331.5 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Start350.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish350.2 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Finish350.2 ft. AMH - Downstream Manhole, Survey Ends - 08 0338

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    87.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, at 08 o'clock, within 8 inches of joint: YES

    87.3 ft. - Surface Aggregate Projecting, at 08 o'clock, within 8 inches of joint: YES

  • Deposits Settled Other,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: NO, Start

    331.5 ft. - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Start

Observations (11)

DistanceCodeObservation
0MWM
350.2SAV
331.5DSZ
350.2DSZ
240.7TFA
350.2AMH08 0338
87.3SAV
2.2MGOMAG COAT
0MWL
0AMH08 0339
87.3SAP

Properties (4)

additional_info
SC364712
custom_field_two
3
customer
LACSD
datetime
2018-07-27T01:02:53-07:00