Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 27, 2018, 08:33 AM
  • 08 0338_08 0337 _27072018_014704.mp4

Date
07/27/2018
W/O
717824
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00003
PipeID
P00388
Time
1:33 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5800
Sewer Name
08 DAVIDSON CITY TRUNK, SECTS 1,2,&3
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
14
Purpose
Routine Assessment
Project
WO_717824_TV08104_AUG2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
08 0338
Downstream MH
08 0337
Dir. of Survey
Downstream
Length Surveyed
302.7 ft.
Total Length
302.7 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
186
O&M Index
2
O&M Quick
2J00
O&M Rating
108
Overall Index
3
Overall Quick
Overall Rating
294
Pipe schematic from manhole 08 0338 to 08 0337
MH: 08 0338MH: 08 0337downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 03380 ft. MWL - Water Level, 15 %of cross sectional area3.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start24 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"35 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start220 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"220 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO226.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"266.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"294.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO294.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6"302.7 ft. AMH - Downstream Manhole, Survey Ends - 08 0337302.7 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish302.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Other,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    35 ft. - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO

    220 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO

    294.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO

Observations (15)

DistanceCodeObservation
0MWM
266.1TFA
294.7SAP
302.7AMH08 0337
3.6SAV
35DSZ
226.5TF
220TF
302.7DSZ
294.7TF
0AMH08 0338
302.7SAV
24TF
220SAP
0MWL

Properties (4)

additional_info
SC364712
custom_field_two
3
customer
LACSD
datetime
2018-07-27T01:33:41-07:00