Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 25, 2018, 09:25 AM
  • 29 0195_29 0194 _25072018_024503.mpg

Date
07/25/2018
W/O
717713
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z01025
PipeID
P24093
Time
2:25 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5322
Sewer Name
29 28TH STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
WO_717713_TV29056_AUG2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0194
Downstream MH
29 0195
Dir. of Survey
Upstream
Length Surveyed
286.3 ft.
Total Length
286.3 ft.
Structural Index
3
Structural Quick
413J
Structural Rating
163
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
163
Pipe schematic from manhole 29 0194 to 29 0195
MH: 29 0194MH: 29 0195upstream0 ft. AMH - Upstream Manhole, Survey Ends - 29 01950 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish5.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"7.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"56 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"58.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"94.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6"107 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"109.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"154.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"156.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"205.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"209.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"226.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"257.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"259.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start267.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES271.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES286.3 ft. MWL - Water Level, 5 %of cross sectional area286.3 ft. AMH - Downstream Manhole, Survey Begins - 29 0194286.3 ft. MWM - Water Mark, 5 %of cross sectional area

Observation photos (3)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    14.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    18.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    27.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
18.9CM
230.3TFC
0MWL
228.1TFC
60.1TF
191.7TB
176.9TFC
281.2TF
286.3AMH29 0195
28.6TFC
14.6FM
0AMH29 0194
129.4TFC
80.8TFC
131.5TF
27.1CM
286.3CM
278.6TFA
179.3TFC
0MWM
76.5TF

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2018-07-25T02:25:06-07:00