Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 20, 2018, 07:41 AM
  • J 0048_J 0046 _20072018_010729.mp4

Date
07/20/2018
W/O
712548
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00062
PipeID
P11625
Time
12:41 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5785
Sewer Name
J JOINT OUTFALL J - UNIT 2C
City
LOMITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
32
Purpose
Routine Assessment
Project
WO_712548_TV05287_JUL2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
J 0048
Downstream MH
J 0046
Dir. of Survey
Downstream
Length Surveyed
743.8 ft.
Total Length
743.8 ft.
Structural Index
3
Structural Quick
513\
Structural Rating
446
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
446
Pipe schematic from manhole J 0048 to J 0046
MH: J 0048MH: J 0046downstream0 ft. AMH - Upstream Manhole, Survey Begins - J 00480 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK10.9 ft. MGO - General Observation - MAG COAT10.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start683.1 ft. SRV - Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: NO743.8 ft. AMH - Downstream Manhole, Survey Ends - J 0046743.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish743.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: NO

    683.1 ft. - Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: NO

Observations (11)

DistanceCodeObservation
743.8AMHJ 0046
10.9MGOMAG COAT
743.8SAP
0AMHJ 0048
683.1SRV
0MGOCONNECTION AT MH 9 O'CLOCK
0MWM
0MWL
743.8MGOCONNECTION AT MH 9 O'CLOCK
10.9SAP
0MGOCONNECTION AT MH 3 O'CLOCK

Properties (4)

additional_info
SC3549696
custom_field_two
2
customer
LACSD
datetime
2018-07-20T00:41:41-07:00