Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 20, 2018, 04:54 AM
  • 15 0419_15 0934 _19072018_221511.mp4

Date
07/19/2018
W/O
718062
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00607
PipeID
P12345
Time
9:54 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5873
Sewer Name
15 HILL DRIVE EXTENSION TRUNK
City
ROSEMEAD
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
27
Purpose
Routine Assessment
Project
WO_718062_TV15221_AUG2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0419
Downstream MH
15 0934
Dir. of Survey
Downstream
Length Surveyed
284 ft.
Total Length
284 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
5131
O&M Rating
12
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 15 0419 to 15 0934
MH: 15 0419MH: 15 0934downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 04192 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start69.1 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"69.1 ft. RFC - Roots Fine Connection, from 11 to 01 o'clock, within 8 inches of joint: YES79.2 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 25 %, within 8 inches of joint: YESR79.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start84.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"86 ft. RFJ - Roots Fine Joint, from 03 to 09 o'clock, within 8 inches of joint: YESR167.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"180.2 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"234.3 ft. MWM - Water Mark, 90 %of cross sectional area254 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"271.1 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"282.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish282.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish284 ft. AMH - Downstream Manhole, Survey Ends - 15 0934284 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Roots Fine Connection, from 11 to 01 o'clock, within 8 inches of joint: YES

    69.1 ft. - Roots Fine Connection, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Roots Medium Joint, from 08 to 04 o'clock, 25 %, within 8 inches of joint: YESR

    79.2 ft. - Roots Medium Joint, from 08 to 04 o'clock, 25 %, within 8 inches of joint: YESR

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    79.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 03 to 09 o'clock, within 8 inches of joint: YESR

    86 ft. - Roots Fine Joint, from 03 to 09 o'clock, within 8 inches of joint: YESR

  • Water Mark, 90 %of cross sectional area

    234.3 ft. - Water Mark, 90 %of cross sectional area

Observations (19)

DistanceCodeObservation
86RFJ
84.1TFC
0MWL
69.1TBA
234.3MWM
79.2RMJ
0MWM
2DAGS
69.1RFC
271.1TBA
180.2TBA
284AMH15 0934
282.7CM
0AMH15 0419
254TFA
282.7DAGS
284MGOACTIVE CONNECTION AT MH 3 O'CLOCK
167.1TFC
79.3CM

Properties (4)

additional_info
SC359741
custom_field_two
3
customer
LACSD
datetime
2018-07-19T21:54:05-07:00