Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 3, 2018, 10:09 AM
  • H 0727_H 0726 _03072018_033229.mp4

Date
07/03/2018
W/O
712465
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00941
PipeID
P11136
Time
3:09 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5764
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
30
Purpose
Routine Assessment
Project
WO_712465_TV22077_JUL2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
28 in.
Width
28 in.
Upstream MH
H 0727
Downstream MH
H 0726
Dir. of Survey
Downstream
Length Surveyed
815.8 ft.
Total Length
815.8 ft.
Structural Index
3
Structural Quick
3`00
Structural Rating
489
O&M Index
3
O&M Quick
3_00
O&M Rating
480
Overall Index
3
Overall Quick
Overall Rating
969
Pipe schematic from manhole H 0727 to H 0726
MH: H 0727MH: H 0726downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 07270 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start16.1 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start815.8 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish815.8 ft. AMH - Downstream Manhole, Survey Ends - H 0726815.8 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Other,  15 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    16.1 ft. - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
815.8SAV
0MWM
2.1MGOMAG COAT
0AMHH 0727
0MWL
815.8AMHH 0726
815.8DSZ
2.1SAV
16.1DSZ

Properties (4)

additional_info
SC359673
custom_field_two
3
customer
LACSD
datetime
2018-07-03T03:09:39-07:00