Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 19, 2018, 07:55 AM
  • 17 0083_17 0082 _19072018_010732.mp4

Date
07/19/2018
W/O
711943
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00669
PipeID
P13801
Time
12:55 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5872
Sewer Name
17 LINCOLN AVENUE TRUNK
City
ALTADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
03
Purpose
Routine Assessment
Project
WO_711943_TV17009_JUL2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
17 0083
Downstream MH
17 0082
Dir. of Survey
Downstream
Length Surveyed
185.5 ft.
Total Length
185.5 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 17 0083 to 17 0082
MH: 17 0083MH: 17 0082downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 17 00830 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start18.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"22.3 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"25 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"49 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"76.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"112.2 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"128.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"151.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"183.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish183.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish185.5 ft. AMH - Downstream Manhole, Survey Ends - 17 0082185.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
151.5TFC
183.7CM
183.7DAGS
22.3TB
49TFC
0MWM
18.7TF
112.2TF
76.4TFC
185.5AMH17 0082
6.9CM
185.5MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0AMH17 0083
0MWL
128.2TFC
2DAGS
25TFC

Properties (4)

additional_info
SC359740
custom_field_two
3
customer
LACSD
datetime
2018-07-19T00:55:42-07:00