Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 27, 2018, 07:43 PM
  • 05 1182_05 1204_7272018_124704.mp4

Date
07/27/2018
W/O
0717904
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00514
PipeID
P06422
Time
12:43 PM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7770
Sewer Name
05 ROSECRANS AVENUE TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
20180727SHO_ROSECRANS_AVENUE_TRUNK
Material
NRCP
Shape
Circular
Height
9.479999542236328 in.
Upstream MH
05 1182
Downstream MH
05 1204
Dir. of Survey
Downstream
Length Surveyed
270.1 ft.
Total Length
270.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 05 1182 to 05 1204
MH: 05 1182MH: 05 1204downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - OPEN CONNECTION IN THE MH @ 30 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - MH 118244.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"54.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"97.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"110.4 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6"153.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"156.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"203.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"206.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"254.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"257.4 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6"270.1 ft. AMH - Downstream Manhole, Survey Ends - MH 1204

Observations (15)

DistanceCodeObservation
153.5TFA
254.6TF
206.5TFA
257.4TFD
156.6TF
203.8TF
54.6TFA
0MWL
44.4TF
270.1AMHMH 1204
0MGOOPEN CONNECTION IN THE MH @ 3
0MWM
0AMHMH 1182
110.4TFD
97.9TF

Properties (4)

custom_field_three
LINER IS IN GOOD CONDITION
custom_field_two
4
customer
LACSD
datetime