Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2018, 01:55 PM
  • 05 1190_05 1189_7262018_071117.mp4

Date
07/26/2018
W/O
0717904
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00514
PipeID
P06430
Time
6:55 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7768
Sewer Name
05 ROSECRANS AVENUE TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
20180726SHO_ROSECRANS_AVENUE_TRUNK
Material
NRCP
Shape
Circular
Height
9.5600004196167 in.
Upstream MH
05 1190
Downstream MH
05 1189
Dir. of Survey
Downstream
Length Surveyed
318.6 ft.
Total Length
318.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 05 1190 to 05 1189
MH: 05 1190MH: 05 1189downstream0 ft. AMH - Upstream Manhole, Survey Begins - MH 11900 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area12.5 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6"37.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"64.3 ft. MGO - General Observation - LINER TAPE IS LOOSE65.2 ft. LFAC - Lining Failure Abandoned Connection, at 10 o'clock, within 8 inches of joint: NO104.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"155.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"156.1 ft. LFAC - Lining Failure Abandoned Connection, at 10 o'clock, within 8 inches of joint: NO206.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 10 o'clock, , within 8 inches of joint: NO208.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"259 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6"269.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"318.6 ft. AMH - Downstream Manhole, Survey Ends - MH 1189318.6 ft. MGO - General Observation - OPEN CONNECTION IN THE MH @ 3

Observation photos (1)

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    37.1 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (16)

DistanceCodeObservation
65.2LFAC
0AMHMH 1190
208.9TF
64.3MGOLINER TAPE IS LOOSE
318.6AMHMH 1189
37.1TF
206.7DAGS
318.6MGOOPEN CONNECTION IN THE MH @ 3
0MWM
104.4TF
0MWL
12.5TFD
269.2TFA
259TFD
155.7TF
156.1LFAC

Properties (6)

custom_field_three
LINER IS IN GOOD CONDITION
custom_field_two
4
customer
LACSD
datetime
2018-07-26T06:55:00-07:00
lining
CIPP
year_laid
20050531