Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 24, 2018, 08:12 AM
  • 08 0002_08 0683 _24012018_002509.mp4

Date
01/24/2018
W/O
679386
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00016
PipeID
P24998
Time
12:12 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5418
Sewer Name
08 MAIN STREET TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
WO_679386_TV08115_JAN2018
Sewer Type
Gravity
Material
RCP-CTL
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
08 0002
Downstream MH
08 0683
Dir. of Survey
Downstream
Length Surveyed
259 ft.
Total Length
259 ft.
Structural Index
3
Structural Quick
5H3I
Structural Rating
470
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
470
Pipe schematic from manhole 08 0002 to 08 0683
MH: 08 0002MH: 08 0683downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 00020 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 40 %of cross sectional area6.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start36.9 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start259 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish259 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK259 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish259 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish259 ft. AMH - Downstream Manhole, Survey Ends - 08 0683

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    36.9 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0MGOCONNECTION AT MH 9 O'CLOCK
0MWL
0AMH08 0002
36.9SRV
259SSS
259MGOCONNECTION AT MH 9 O'CLOCK
259SAP
259SRV
6.9SSS
6.9SAP
0MGOCONNECTION AT MH 3 O'CLOCK
259AMH08 0683
0MWM

Properties (4)

additional_info
SC347052
custom_field_two
2
customer
LACSD
datetime
2018-01-24T00:12:38-08:00